Google Cloud outage, 15 July 2026
The Google Cloud outage of 15 July 2026: what failed, why, and what Google Cloud changed, from its own incident report.
- Provider
- Google Cloud
- Date
- Duration, hours
- 14.9
- Cause
- Power/cooling
- Regions
- europe-west4-a (Netherlands)
Google Cloud europe-west4-a power and cooling outage (15 July 2026). The disruption lasted about 14 hours 55 minutes, according to Google Cloud’s own timeline.
What happened. A 3 ms utility voltage drop tripped breakers on both feeds; one side’s diesel rotary UPS failed and a row lost all power. The chiller controller also went offline, cooling stopped (the redundant source was down for construction), the hall reached 44°C, and machines were shut down.
What changes. Google is investigating the DRUPS and overload failures, checking chiller pump control redundancy, adding earlier power/cooling alerts, and improving automated thermal shutdown.
Questions
What caused the Google Cloud outage in July 2026?
A 3 ms utility voltage drop tripped breakers on both feeds; one side’s diesel rotary UPS failed and a row lost all power.
Which services were affected?
Google Cloud VMware Engine, Bare Metal Solution, Google Cloud NetApp Volumes.
Read how shared dependencies spread a failure in why one cloud outage can break unrelated apps, or browse the outage archive.
- Started (UTC)
- 2026-07-15 23:39 UTC
- Resolved (UTC)
- 2026-07-16 14:34 UTC
- Services affected
- Google Cloud VMware Engine, Bare Metal Solution, Google Cloud NetApp Volumes
- Incident report
- status.cloud.google.com
- Sources
Source Link Google Cloud incident report https://status.cloud.google.com/incidents/3BvH3LVGcupoYqV6F4Nw