14.9
Cause
Power/cooling
Regions
europe-west4-a (Netherlands)

Google Cloud europe-west4-a power and cooling outage (15 July 2026). The disruption lasted about 14 hours 55 minutes, according to Google Cloud’s own timeline.

What happened. A 3 ms utility voltage drop tripped breakers on both feeds; one side’s diesel rotary UPS failed and a row lost all power. The chiller controller also went offline, cooling stopped (the redundant source was down for construction), the hall reached 44°C, and machines were shut down.

What changes. Google is investigating the DRUPS and overload failures, checking chiller pump control redundancy, adding earlier power/cooling alerts, and improving automated thermal shutdown.

Questions

What caused the Google Cloud outage in July 2026?

A 3 ms utility voltage drop tripped breakers on both feeds; one side’s diesel rotary UPS failed and a row lost all power.

Which services were affected?

Google Cloud VMware Engine, Bare Metal Solution, Google Cloud NetApp Volumes.

Read how shared dependencies spread a failure in why one cloud outage can break unrelated apps, or browse the outage archive.

Started (UTC)
2026-07-15 23:39 UTC
Resolved (UTC)
2026-07-16 14:34 UTC
Services affected
Google Cloud VMware Engine, Bare Metal Solution, Google Cloud NetApp Volumes
Incident report
status.cloud.google.com
Sources
SourceLink
Google Cloud incident reporthttps://status.cloud.google.com/incidents/3BvH3LVGcupoYqV6F4Nw