Google Cloud outage, 20 October 2026

The Google Cloud outage of 20 October 2026: cause, impact and fixes, from Google’s own incident report.

Provider
Google Cloud
Date
Duration, hours
6.1
Cause
Power/cooling
Regions
europe-west2-b (London); wider europe-west2 region

Google Cloud europe-west2-b power loss (20 October 2026). The disruption lasted 6 hours 8 minutes, according to Google Cloud’s own incident report. It began at 06:00 UTC and was resolved at 12:08 UTC; a small tail of isolated workloads recovered later. A data center facility that hosts europe-west2-b, a zone within the europe-west2 cloud region, experienced an external electrical power disruption.

What happened next. A voltage-sensing design flaw and a misconfigured controller kept the generators from starting, so UPS batteries carried the load until they ran out. Failover from the dark zone then caused latency and 500 and 503 errors across the wider London region.

What changes. Google reconfigured and validated the controller, updated its emergency operating procedures, froze planned maintenance at sites with similar designs and is reviewing controller configurations at those sites.

Questions

What caused the Google Cloud outage in October 2026?

An external underground cable fault cut the one utility feed the London facility was running on during maintenance, and a controller misconfiguration stopped the backup generators from starting.

How long did it last?

6 hours 8 minutes, from 07:00 to 13:08 BST (06:00 to 12:08 UTC) on 20 October 2026.

Which services were affected?

Workloads in europe-west2-b became unreachable, and 38 products in europe-west2 were listed as affected, including Compute Engine, Persistent Disk, GKE, BigQuery, Cloud SQL, Cloud Storage and Spanner.

Read how shared dependencies spread a failure in why one cloud outage can break unrelated apps, or browse the outage archive.

Started (UTC)
2026-10-20 06:00 UTC
Resolved (UTC)
2026-10-20 12:08 UTC
Services affected
Workloads in europe-west2-b; 38 products in europe-west2, including Compute Engine, Persistent Disk, GKE, BigQuery, Cloud SQL, Cloud Storage, Spanner, Cloud Run and Pub/Sub
Incident report
status.cloud.google.com
Sources
SourceLink
Google Cloud incident reporthttps://status.cloud.google.com/incidents/Xs2XTHzAVC9YnafnPyzj

Source: every outage is taken from the provider’s own post-incident report, linked under Sources on its page. Times and durations are as the provider states them.